Skip to content

Xemex Smart Connect#

This guide explains how to install and configure the A1 Smart Connect (A1/P1) on a Fluvius meter, and how to confirm the device is working.

What you need#

  • A1 Smart Connect device
  • Supplied RJ12-to-RJ12 cable (straight-wired)
  • Ethernet (UTP) cable
  • A laptop on the same network (for IP scan + web browser access)

1. Physical installation#

  1. Connect the A1 Smart Connect to the Fluvius meter using the supplied RJ12 cable.

    • Connect it to the A1/P1 in port of the Xemex module.
  2. Connect the A1 Smart Connect to your local network using a standard Ethernet (UTP) cable.

  3. Plug the Ethernet cable into a network switch or router.

Image

2. Find the device IP address or Hostname#

You can access the web interface using either the device's IP address or hostname.

Option 1: Using the IP address

  1. Run an IP scan on your local network from your laptop.
  2. Identify the device in the scan results.

If you cannot find the IP address:

  • Press and hold the reset button for 10 seconds.
  • The device will revert to its factory IP range: 169.254.x.x.

Option 2: Using the hostname

  1. Scan the network to identify all hostnames. The Xemex should have a hostname following this pattern: smart-connect-xmxkaac00000xxxx.local
  2. Alternatively, enter the dummy hostname in a browser: http://smart-connect or http://smart-connect.local. This will load a page showing the actual hostname of the Xemex Smart Connect dongle, e.g., smart-connect-xmxkaac00000xxxx.local

3. Open the web interface#

  1. Open a browser and navigate to the device IP address or Hostname
  2. Log in using the unique password printed on the device.

Image Image

4. Configure network settings#

Recommendation: Use DHCP setting whenever possible.

If the network rules do not allow DHCP configuration, use the following steps to configure a static IP for the smart dongle:

  1. In the web interface, open Network settings.
  2. Select the network type: Ethernet
  3. Configure IP mode: Static IP or DHCP based
  4. Click Save network settings.

Image Image

5. Disable MQTT#

  1. In the web interface, locate the MQTT settings.
  2. Disable MQTT.
  3. Save the setting.

Image

6. Reboot and verify operation#

  1. Reboot the device.

  2. Re-open the web interface and confirm:

    • Network settings are saved.
    • Meter connection status is OK.

Image

If everything is set up correctly, the Smart Connect should show flashing green LEDs.

7. Attention Points#

The complete installation guide for the Xemex Smart Connect is available here: www.xemex.eu

Share these details with Octave after installation:

  • Xemex IP address
  • Fluvius meter transformation factors (current and voltage)

    Image

Extra photos#

Image Image Image