Kenter COM350#

The Kenter COM350 is a communication module on a fiscal meter (the official billing meter). It reads all relevant measurement data from the electricity meter and makes this data available over Modbus TCP.

Supported assets#

Model Modbus TCP Modbus RTU Validated
COM350

Configuration#

Kenter configures the COM350 for the site. To connect the COM350 correctly to the Octave EMS, Kenter must receive the required settings before the installation. Send Kenter these details:

  • Network settings: the IP address, subnet mask and default gateway for the COM350 on the local network of the Octave EdgeBox.
  • Modbus parameters: only if the site needs values that are different from the defaults. The Octave EMS uses unit ID 1 and Modbus TCP port 502.

Kenter supplies a list of the available Modbus registers with the module.

Share these details with Octave after installation:

  • COM350 IP address
  • Modbus TCP port and unit ID
  • Current and voltage transformer ratios of the meter

Modbus registers#

The Octave EMS reads these registers from the COM350. Import is energy taken from the grid. Export is energy sent to the grid.

All values are holding registers. The EMS reads them in two blocks: 1000–1055 and 1130–1199. The COM350 sends FLOAT32 values with the two 16-bit words swapped (low word first). Use this word order if you read the meter with a different Modbus tool.

Address Measurement Data type Unit
1000 Total active energy, import INT64 Wh
1020 Total active energy, export INT64 Wh
1048 Total reactive energy, import INT64 varh
1052 Total reactive energy, export INT64 varh
1130 Current L1 FLOAT32 A
1132 Current L2 FLOAT32 A
1134 Current L3 FLOAT32 A
1136 Voltage L1-N FLOAT32 V
1138 Voltage L2-N FLOAT32 V
1140 Voltage L3-N FLOAT32 V
1142 Grid frequency FLOAT32 Hz
1144 Total active power, import FLOAT32 W
1146 Active power L1, import FLOAT32 W
1148 Active power L2, import FLOAT32 W
1150 Active power L3, import FLOAT32 W
1152 Total active power, export FLOAT32 W
1154 Active power L1, export FLOAT32 W
1156 Active power L2, export FLOAT32 W
1158 Active power L3, export FLOAT32 W
1160 Total reactive power, import FLOAT32 var
1162 Reactive power L1, import FLOAT32 var
1164 Reactive power L2, import FLOAT32 var
1166 Reactive power L3, import FLOAT32 var
1168 Total reactive power, export FLOAT32 var
1170 Reactive power L1, export FLOAT32 var
1172 Reactive power L2, export FLOAT32 var
1174 Reactive power L3, export FLOAT32 var
1192 Total power factor FLOAT32 -
1194 Power factor L1 FLOAT32 -
1196 Power factor L2 FLOAT32 -
1198 Power factor L3 FLOAT32 -

The EMS does not show the import and export power values separately. It calculates the net power as import minus export, for the total and for each phase.

The Octave EMS applies the transformer ratios to the values it reads:

  • Current: multiplied by the current transformer ratio.
  • Voltage: multiplied by the voltage transformer ratio.
  • Energy and power: multiplied by the current transformer ratio and by the voltage transformer ratio.
  • Frequency and power factor: not scaled.

For help with the setup, email development@octave.energy.