# Kenter COM350

The Kenter COM350 is a communication module on a fiscal meter (the official billing meter). It reads all relevant measurement data from the electricity meter and makes this data available over Modbus TCP.

## Supported assets

| Model | Modbus TCP | Modbus RTU | Validated |
| --- | :---: | :---: | :---: |
| COM350 |  |  |  |

## Configuration

Kenter configures the COM350 for the site. To connect the COM350 correctly to the Octave EMS, Kenter must receive the required settings before the installation. Send Kenter these details:

- **Network settings:** the IP address, subnet mask and default gateway for the COM350 on the local network of the Octave EdgeBox.
- **Modbus parameters:** only if the site needs values that are different from the defaults. The Octave EMS uses unit ID 1 and Modbus TCP port 502.

Kenter supplies a list of the available Modbus registers with the module.

Share these details with Octave after installation:

- COM350 IP address
- Modbus TCP port and unit ID
- Current and voltage transformer ratios of the meter

## Modbus registers

The Octave EMS reads these registers from the COM350. Import is energy taken from the grid. Export is energy sent to the grid.

All values are holding registers. The EMS reads them in two blocks: 1000–1055 and 1130–1199. The COM350 sends FLOAT32 values with the two 16-bit words swapped (low word first). Use this word order if you read the meter with a different Modbus tool.

| Address | Measurement | Data type | Unit |
| ---: | --- | --- | --- |
| 1000 | Total active energy, import | INT64 | Wh |
| 1020 | Total active energy, export | INT64 | Wh |
| 1048 | Total reactive energy, import | INT64 | varh |
| 1052 | Total reactive energy, export | INT64 | varh |
| 1130 | Current L1 | FLOAT32 | A |
| 1132 | Current L2 | FLOAT32 | A |
| 1134 | Current L3 | FLOAT32 | A |
| 1136 | Voltage L1-N | FLOAT32 | V |
| 1138 | Voltage L2-N | FLOAT32 | V |
| 1140 | Voltage L3-N | FLOAT32 | V |
| 1142 | Grid frequency | FLOAT32 | Hz |
| 1144 | Total active power, import | FLOAT32 | W |
| 1146 | Active power L1, import | FLOAT32 | W |
| 1148 | Active power L2, import | FLOAT32 | W |
| 1150 | Active power L3, import | FLOAT32 | W |
| 1152 | Total active power, export | FLOAT32 | W |
| 1154 | Active power L1, export | FLOAT32 | W |
| 1156 | Active power L2, export | FLOAT32 | W |
| 1158 | Active power L3, export | FLOAT32 | W |
| 1160 | Total reactive power, import | FLOAT32 | var |
| 1162 | Reactive power L1, import | FLOAT32 | var |
| 1164 | Reactive power L2, import | FLOAT32 | var |
| 1166 | Reactive power L3, import | FLOAT32 | var |
| 1168 | Total reactive power, export | FLOAT32 | var |
| 1170 | Reactive power L1, export | FLOAT32 | var |
| 1172 | Reactive power L2, export | FLOAT32 | var |
| 1174 | Reactive power L3, export | FLOAT32 | var |
| 1192 | Total power factor | FLOAT32 | \- |
| 1194 | Power factor L1 | FLOAT32 | \- |
| 1196 | Power factor L2 | FLOAT32 | \- |
| 1198 | Power factor L3 | FLOAT32 | \- |

The EMS does not show the import and export power values separately. It calculates the net power as import minus export, for the total and for each phase.

The Octave EMS applies the transformer ratios to the values it reads:

- **Current:** multiplied by the current transformer ratio.
- **Voltage:** multiplied by the voltage transformer ratio.
- **Energy and power:** multiplied by the current transformer ratio and by the voltage transformer ratio.
- **Frequency and power factor:** not scaled.

For help with the setup, email .