# Xemex Smart Connect

This guide explains how to install and configure the **A1 Smart Connect (A1/P1)** on a **Fluvius meter**, and how to confirm the device is working.

The Xemex Smart Connect P1/A1 is a compact module that converts Dutch and Belgian Smart Meter P1/A1 messages into Modbus TCP or MQTT. It supports DSMR 4.2+ in the Netherlands and the EMUCS standard in Belgium. The Smart Connect also features a P1/A1 output port to replicate the original message, allowing other P1/A1 devices to remain functional.

It connects to the Smart Meter via an RJ12-to-RJ12 cable and is typically powered through the meter's P1/A1 port. In specific cases where this is insufficient (see [Power input](<#1-physical-installation>)), an external USB-C power supply can be used.

## Supported assets

| Model | Modbus TCP | Modbus RTU | Validated |
| --- | :---: | :---: | :---: |
| Smart Connect |  |  |  |

## What you need

- A1 Smart Connect device
- Supplied RJ12-to-RJ12 cable **(straight-wired)**
- Ethernet (UTP) cable
- A laptop on the same network (for IP scan + web browser access)

## 1\. Physical installation

**Network cables**

1. Connect the A1 Smart Connect to the Fluvius meter using the supplied RJ12 cable.

   - Connect it to the A1/P1 in port of the Xemex module.
2. Connect the A1 Smart Connect to your local network using a standard Ethernet (UTP) cable.
3. Plug the Ethernet cable into a network switch or router that is on the same network as the Octave Edgebox.

[![Image](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/c6889584-image.png>)](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/c6889584-image.png>)

**Power input**

This port provides power to the device. It is mandatory to connect a USB-C power supply when using the P1/A1-OUT function (the case in most installations), with a DSMR 4.2 meter, or with TIC input. Only a P1/A1 input from an SMR 5.x meter, without P1/A1-OUT, can run on the meter's power alone. Always use certified USB-C power supplies and cables to ensure safe and reliable operation.

The table below describes when an external USB-C power supply should be used.

| Usage | No | Yes |
| --- | :---: | :---: |
| P1/A1 IN (SMR 5.x) | ✓ |  |
| P1/A1 IN (DSMR 4.2) |  | ✓ |
| P1/A1 OUT |  | ✓ |
| TIC IN |  | ✓ |

## 2\. Find the device IP address or Hostname

You can access the web interface using either the device's IP address or hostname.

**Option 1: Using the IP address**

1. Run an IP scan on your local network from your laptop.
2. Identify the device in the scan results.

If you cannot find the IP address:

- Press and hold the **reset button for 10 seconds**.
- The device will revert to its factory IP range: **169.254.x.x**.

**Option 2: Using the hostname**

1. Scan the network to identify all hostnames. The Xemex should have a hostname following this pattern: `smart-connect-xmxkaac00000xxxx.local`
2. Alternatively, enter the dummy hostname in a browser: `http://smart-connect` or `http://smart-connect.local`. This will load a page showing the actual hostname of the Xemex Smart Connect dongle, e.g., `smart-connect-xmxkaac00000xxxx.local`

## 3\. Open the web interface

1. Open a browser and navigate to the device IP address or Hostname
2. Log in using the **unique password printed on the device**.

[![Image](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/35033f6a-image.png>)](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/35033f6a-image.png>) [![Image](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/52788419-image.png>)](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/52788419-image.png>)

## 4\. Configure network settings

**Recommendation:** Use **DHCP** setting whenever possible.

If the network rules do not allow DHCP configuration, use the following steps to configure a static IP for the smart dongle:

1. In the web interface, open **Network settings**.
2. Select the network type: **Ethernet**
3. Configure IP mode: Static IP or DHCP based
4. Click **Save network settings**.

[![Image](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/87709091-image.png>)](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/87709091-image.png>) [![Image](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/799a0b59-image.png>)](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/799a0b59-image.png>)

## 5\. Disable MQTT

1. In the web interface, locate the **MQTT settings**.
2. **Disable MQTT**.
3. Save the setting.

[![Image](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/7c8e23c4-image.png>)](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/7c8e23c4-image.png>)

## 6\. Reboot and verify operation

1. Reboot the device.
2. Re-open the web interface and confirm:

   - Network settings are saved.
   - Meter connection status is **OK**.

[![Image](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/status.png>)](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/status.png>)

If everything is set up correctly, the Smart Connect should show a **continuous green LED**.

| State | Color | Pattern | Description |
| --- | --- | --- | --- |
| Off | \- | \- | Module not powered |
| Power-up | Red | Continuous | Module booting |
| Normal Operation | Green | Continuous | Smart Connect receives P1/A1/TIC data; network is connected and configured. Providing Modbus TCP or MQTT data. |
| AP mode | Blue | Blinking | Module in AP mode |

## 7\. Attention Points

The **complete installation guide** for the Xemex Smart Connect is available here: [www.xemex.eu](<https://www.xemex.eu/inhoud/uploads/2025/10/Smart-Connect-Manual-EN-V1.11.pdf>)

Share these details with Octave after installation:

- Xemex IP address
- Smart Connect UI login credentials
- Fluvius meter transformation factors (current and voltage)

  [![Image](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/ean_meters.png>)](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/ean_meters.png>)

## Extra photos

[![Image](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/extra_1.png>)](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/extra_1.png>) [![Image](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/extra_2.png>)](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/extra_2.png>) [![Image](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/extra_3.png>)](<https://docs.octave.energy/ems/integrations/assets/xemex-smart-connect/extra_3.png>)