# Smappee Genius Flex

Before commissioning, enable the ModbusTCP integration on the Smappee Genius Flex gateway and provide the connection details to your Octave contact.

## Supported assets

| Model | Modbus TCP | Modbus RTU | Validated |
| --- | :---: | :---: | :---: |
| Genius Flex |  |  |  |

## How the connection works

The Genius Flex gateway provides access to the connected Smappee EV chargers through the ModbusTCP app. The connection uses the gateway's **wired IP address** and the **host port assigned by the app**.

## 1\. Install the ModbusTCP app

1. Open the Smappee app.
2. Open the Genius Flex location under **Settings**.
3. Go to **Control**.
4. Open the **Smappee Store**.
5. Select the **ModbusTCP** app.
6. Tap **Install integration**.
7. Review the permissions and tap **Continue**.
8. Save the generated username and password immediately. They are shown only once. If they are lost, the integration must be reinstalled.
9. Open the app's **Activity** screen and record the assigned host port.

For more information, see [How do I install an app from the Smappee Store?](<https://support.smappee.com/hc/en-gb/articles/52714305480852-How-do-I-install-an-app-from-the-Smappee-Store>).

> [!WARNING]
>
> Do not assume the port is **502**. Copy the actual host port from the ModbusTCP app's **Activity** screen.

## 2\. Provide the installation details

Provide the following information to your Octave contact:

| Information | What to provide |
| --- | --- |
| Gateway IP address | Wired IP address of the Genius Flex gateway |
| Host port | Port shown in the ModbusTCP app's Activity screen |
| Integration credentials | Generated username and password; share securely, not in this guide |
| Charging stations | Total number of stations connected through the gateway |
| Sockets | Number of sockets on each station: one or two |
| Modbus addressing | Confirm the station/socket-to-unit-ID mapping with the installer, including the first unit ID and any gaps |
| Gateway serial number | Genius Flex serial number, needed for the control refresh request below |

Ensure the gateway's wired IP address and assigned host port are reachable from the installed energy-management equipment. Coordinate any required network access with the installer or network administrator.

## 3\. Request a faster refresh interval if control is required

For monitoring only, the default register refresh interval may be sufficient.

For energy-management control, ask **Smappee support** to reduce the register refresh interval from **15 seconds to 2 seconds**. Include the **Genius Flex serial number** in the request.

## 4\. Support commissioning

During commissioning:

1. Make sure the ModbusTCP app is installed and active.
2. Confirm the gateway's wired IP address, assigned port, and charger addressing details with the commissioning contact.
3. Connect a vehicle to a charger when requested.
4. Help verify that the reported charging power and currents match the values visible in Smappee.
5. If control is enabled, coordinate a temporary charging-current adjustment with the commissioning contact and confirm normal settings are restored after the test.

## Troubleshooting

| Issue | What to check |
| --- | --- |
| Cannot connect to the gateway | Confirm the ModbusTCP app is installed and active; verify the wired IP address and network access |
| Port 502 does not respond | Use the actual host port from the app's Activity screen |
| Some chargers are missing | Confirm the number of stations, sockets per station, and station/socket-to-unit-ID mapping with the installer |
| Charging-current changes are slow | Confirm Smappee support has changed the register refresh interval to 2 seconds |
| Monitoring works but control does not | Ask the commissioning contact to check integration permissions, charger addressing, and the Smappee control setup |
| Integration credentials are lost | Reinstall the integration to generate new credentials and securely provide the updated details to the commissioning contact |