ABB TRIO 50.0/60.0 TL/TM#

Supported assets#

Model Modbus TCP Modbus RTU Validated
TRIO 50.0/60.0 TL/TM

Configuration#

Before commissioning, set the inverter's RS485 port to Modbus RTU, connect it to an RS485-to-Ethernet gateway, and provide the connection details to your Octave contact.

This guide applies to the TRIO-50.0/60.0-TL-OUTD and TRIO-50.0/60.0-TM-OUTD inverter families. These inverters can be monitored and controlled by an external Modbus RTU master over an RS485 serial line.

Modbus RTU is a master-slave protocol: the master sends a request and the inverter (the slave) answers. The inverter supports only the Modbus features described in the ABB register map. It does not support other Modbus features.

The inverter has two separate sets of registers:

  • Holding registers are used mainly for control. You read them with function 3 and write them with function 6 or 16. All commands to the inverter use holding registers.
  • Input registers are read-only. You read them with function 4. They contain the inverter's status and measurements.

How the connection works#

The inverter communicates through its RS485 port with the Modbus RTU protocol. It does not have a network port for Modbus.

An RS485-to-Ethernet gateway (for example, a Waveshare module) connects the inverter to the site network. The gateway converts Modbus TCP requests from the Octave EMS into Modbus RTU requests for the inverter.

Octave EMS ─ (Ethernet, Modbus TCP) - Gateway ─ (RS485, Modbus RTU) ─ Inverter

What you need#

Item Details
RS485-to-Ethernet gateway For example, a Waveshare RS485 to Ethernet module
RS485 cable Twisted pair with a ground wire
Aurora Manager Lite ABB tool to change the inverter's serial port settings
Laptop (for the test) On the same network as the gateway
Modbus test software QModMaster (free) or Modbus Poll
USB-to-RS485 adapter (optional) Only if you must test the inverter directly, without the gateway

1. Set the inverter's serial port#

Use Aurora Manager Lite to set the RS485 port that the cable connects to (RS485-1 or RS485-2).

Setting Value
Protocol Modbus RTU Slave (not Aurora, not SunSpec)
Slave ID A number from 1 to 247
Baud rate 19200 (default)
Parity None (default)
Data / stop bits 8 / 1 (fixed)

The default protocol is Aurora

The inverter's default protocol is Aurora. When the port is set to Aurora, the inverter ignores all Modbus requests. Change it to Modbus RTU Slave.

Write down the port, slave ID, baud rate and parity. You need them in the next steps.

2. Connect the inverter to the gateway#

Connect the RS485 wires from the inverter's terminal block to the gateway:

Inverter terminal Gateway terminal
+T/R A / D+
−T/R B / D−
RTN GND

Connect the gateway to the site network with an Ethernet cable.

A and B labels

Some manufacturers label A and B the other way around. If the test in step 4 gets no response, swap the A and B wires and try again.

3. Configure the gateway#

Open the gateway's web interface and set the values below.

Setting Value
Serial settings Same as the inverter (baud rate, 8 data bits, parity, 1 stop bit)
Work mode TCP Server
Local port 502
Protocol Modbus TCP to RTU

Use a static IP address for the gateway when possible. If the site has managed IT, give the gateway's IP address and MAC address to the site IT contact.

4. Test the connection#

Do this test from a laptop on the same network as the gateway. It confirms that the inverter answers before commissioning.

  1. Open QModMaster and set it to Modbus TCP.
  2. Enter the values below and send the request.

    Parameter Value
    IP address Gateway IP address
    Port 502
    Unit ID Slave ID from step 1
    Function 04 – Read Input Registers (not 03)
    Start address 999 in QModMaster, or 1000 in Modbus Poll with "PLC addresses (base 1)"
    Quantity 2
  3. Check the result:

    Result What it means
    261, 132 Success. The inverter answers through the gateway.
    Exception 01 or 02 The connection works, but the function code or address is wrong. Check the values above.
    Timeout or no response See Troubleshooting.
  4. Take a screenshot of the result.

If the test fails: test the inverter directly#

This test shows if the problem is in the inverter or in the gateway.

  1. Take photos of the current wiring at the inverter and at the gateway.
  2. Disconnect the RS485 wires from the gateway.
  3. Connect them to a USB-to-RS485 adapter, with the same wiring as in step 2.
  4. In QModMaster, select Modbus RTU. Set the serial port to the values from step 1 and a response timeout of 1000 ms.
  5. Send the same request as above (function 04, address 999, quantity 2).

If you get 261, 132, the inverter works. The problem is in the gateway settings or wiring. Reconnect the wires to the gateway with the same polarity (A/B order) that worked, and check the gateway settings again.

5. Provide the installation details#

Provide the following information to your Octave contact:

Information What to provide
Gateway IP address IP address of the RS485-to-Ethernet gateway
Port Usually 502
Slave ID Slave ID set on the inverter in step 1
Serial settings Port in use, baud rate and parity from step 1
Test result Screenshot of the test in step 4
Gateway configuration Screenshots of all gateway configuration pages (serial and network)
Wiring photos Photos of the inverter terminal block and the gateway terminals

Make sure the gateway's IP address and port are reachable from the installed energy-management equipment. Coordinate any required network access with the installer or network administrator.

Troubleshooting#

Issue What to check
No response from the inverter Make sure the protocol is Modbus RTU Slave, not Aurora. Then check the slave ID and baud rate.
Still no response Swap the A and B wires and try again
Exception 01 or 02 Use function 04, not 03. Check the start address (999, or 1000 with base 1 addressing).
Direct test works, gateway test fails Check that the gateway's serial settings match the inverter, and that the protocol is Modbus TCP to RTU
Cannot reach the gateway on the network Check the gateway's IP address, Ethernet cable and network access
Not sure the inverter is producing Read input register 1050 (address 1049) with function 04. A value of 6 means connected to the grid.