# Kostal Ramping Rate settings

This guide explains how to **reduce the ramp-up time** (faster power increase after start or grid recovery) on **Kostal inverters** using the Kostal web interface / app. The screenshots provided are used as reference.

⚠️ **Important**: Grid-related settings are usually restricted by local grid codes (e.g. BE C10/11). Only certified installers should change these values. Always comply with local regulations.

## Supported assets

| Model | Modbus TCP | Modbus RTU | Validated |
| --- | :---: | :---: | :---: |
| Pico |  |  |  |

## Step 1 - Log in as Installer (required)

Many ramp-up and power gradient parameters are **not visible** unless you are logged in as **Installer**.

1. Open the Kostal interface and go to **Settings**.
2. Select **User management**.
3. Log in using the **Installer** credentials.
4. Confirm that you now see advanced settings such as **Grid settings** and **Power adaptation/controls**.

[![Image](<https://docs.octave.energy/ems/integrations/assets/kostal-ramping-rate/2613e766-d26c486d-62d1-4e48-a284-8d63cbbdc829.png>)](<https://docs.octave.energy/ems/integrations/assets/kostal-ramping-rate/2613e766-d26c486d-62d1-4e48-a284-8d63cbbdc829.png>)

## Step 2 - Navigate to the correct menu

1. Go to **Settings**.
2. Open **Inverter settings**.
3. Select **Grid settings**.

**Menu path overview:**

[![Image](<https://docs.octave.energy/ems/integrations/assets/kostal-ramping-rate/7e0f3449-8f21472b-2ba3-46c8-b5db-3dd2fae17a11.png>)](<https://docs.octave.energy/ems/integrations/assets/kostal-ramping-rate/7e0f3449-8f21472b-2ba3-46c8-b5db-3dd2fae17a11.png>)

You should now see parameters such as:

- Start up time
- Power gradient (%/min)
- Power gradient following grid error (%/min)

## Step 3 - Increase the ramp-up speed

The ramp-up behavior is controlled by the **Power gradient** settings.

### Adjust the following fields:

- **Power gradient (%/min)**

→ Example shown: **18 %/min** or **100 %/min** (after adjustment)

- **Power gradient following grid error (%/min)**

→ Example shown: **8 %/min** or **100 %/min** (after adjustment)

**Grid settings - power gradients:**

[![Image](<https://docs.octave.energy/ems/integrations/assets/kostal-ramping-rate/2e764ff9-image.png>)](<https://docs.octave.energy/ems/integrations/assets/kostal-ramping-rate/2e764ff9-image.png>)

### Recommendation

- Increase these values to allow the inverter to reach full power faster.
- A value of **100 %/min** means the inverter can ramp from 0-100% in approximately one minute.

## Step 4 - Active power control

If ramp-up still feels slow, verify that power control functions are not limiting output.

Go to:

**Settings → Inverter settings → Power adaptation/controls → Active power control**

Check:

- **Power Change Gradient (%/s)**

→ Example shown: **125 %/s** (this is already fast and usually not restrictive)

[![Image](<https://docs.octave.energy/ems/integrations/assets/kostal-ramping-rate/d67a6da5-image.png>)](<https://docs.octave.energy/ems/integrations/assets/kostal-ramping-rate/d67a6da5-image.png>)

## Step 5 - Save and verify

1. Save all modified settings.
2. Restart the inverter if required.
3. Monitor behavior via:

   - **Generation data**
   - **Current power**