# SolarEdge Inverters

This guide is for installers enabling **Modbus TCP** and configuring **RRCR (Remote Power Reduction Control)** on a **SolarEdge inverter** using the **SolarEdge Installer App**.

## Supported assets

| Model | Modbus TCP | Modbus RTU | Validated |
| --- | :---: | :---: | :---: |
| Inverters |  |  |  |

## Prerequisites

- SolarEdge Installer App installed and you can access the site (existing commissioned system).
- Installer credentials / permissions for the inverter.
- The inverter is reachable (remote access may briefly interrupt production).
- You have a plan for **static IP addressing** and you can verify the inverter is online (e.g., IP scanner).

## 1\) Connect to an existing system

1. Open the **SolarEdge Installer App**.
2. On the home screen, select **Connect** → **Existing system**.

   This allows access to an already-commissioned site.

[![Image](<https://docs.octave.energy/ems/integrations/assets/solaredge-inverters/start_screen.png>)](<https://docs.octave.energy/ems/integrations/assets/solaredge-inverters/start_screen.png>)

## 2\) Open the inverter from Inventory

1. Go to **Inventory**.
2. Select the correct **inverter**.
3. Confirm you see:

   - **Manufacturer:** SolarEdge
   - A recent **Last Measurement** timestamp

[![Image](<https://docs.octave.energy/ems/integrations/assets/solaredge-inverters/inverters.png>)](<https://docs.octave.energy/ems/integrations/assets/solaredge-inverters/inverters.png>)

## 3\) Start Remote Access

1. Scroll down on the inverter page and tap **Remote Access**.
2. Press **Connect** and accept the warning.

> [!WARNING]
>
> **Possible restart**
>
> Remote access may restart the inverter or temporarily stop production.

[![Image](<https://docs.octave.energy/ems/integrations/assets/solaredge-inverters/inverter_3.png>)](<https://docs.octave.energy/ems/integrations/assets/solaredge-inverters/inverter_3.png>) [![Image](<https://docs.octave.energy/ems/integrations/assets/solaredge-inverters/remote_access_1.jpeg>)](<https://docs.octave.energy/ems/integrations/assets/solaredge-inverters/remote_access_1.jpeg>)

## 4\) Open the Commissioning menu

Once connected, you’ll be redirected to **Commissioning**. You will mainly use:

- **Site Communication**
- **Power Control**
- **GPIO**

[![Image](<https://docs.octave.energy/ems/integrations/assets/solaredge-inverters/solaredge_sitecommunication.png>)](<https://docs.octave.energy/ems/integrations/assets/solaredge-inverters/solaredge_sitecommunication.png>)

## 5\) Set a static IP and verify the inverter is online

1. Set a **static IP** for the inverter (per site network plan).
2. Verify the inverter is reachable/online (e.g., with an IP scanner).

[![Image](<https://docs.octave.energy/ems/integrations/assets/solaredge-inverters/solaredge_sitecommunication_2.png>)](<https://docs.octave.energy/ems/integrations/assets/solaredge-inverters/solaredge_sitecommunication_2.png>)

## 6\) Enable Modbus TCP

1. Open **Site Communication**.
2. Tap **Modbus TCP port**.
3. Set:

   - **Modbus TCP:** Enabled
   - **Port:** `1502`

[![Image](<https://docs.octave.energy/ems/integrations/assets/solaredge-inverters/solaredge_modbus_tcp_port.png>)](<https://docs.octave.energy/ems/integrations/assets/solaredge-inverters/solaredge_modbus_tcp_port.png>)

**Check**

- Modbus TCP shows **Enabled**
- Port is **1502**

## 7\) Configure GPIO for RRCR

1. Go back to **Site Communication** and open **GPIO**.
2. Set:

   - **Device Type:** Power Reduction Interface (RRCR)
   - **RRCR Mode:** RRCR

[![Image](<https://docs.octave.energy/ems/integrations/assets/solaredge-inverters/solaredge_gpio.png>)](<https://docs.octave.energy/ems/integrations/assets/solaredge-inverters/solaredge_gpio.png>)

**Check**

- RRCR device type is selected
- RRCR mode is set to RRCR

## 8\) Enable RRCR in Power Control

1. Open **Power Control**.
2. Verify:

   - **Grid Control:** Enabled
   - **Power Reduction Interface (RRCR):** Enabled
   - **Reactive Power Reduction Interface:** set as required by the grid code / site requirements
3. Leave **VAR at night** disabled unless specified otherwise.

[![Image](<https://docs.octave.energy/ems/integrations/assets/solaredge-inverters/solaredge_powercontrol.png>)](<https://docs.octave.energy/ems/integrations/assets/solaredge-inverters/solaredge_powercontrol.png>)

**Check**

- RRCR is enabled in Power Control
- Grid control is enabled

## 9\) Final verification (Site Communication overview)

In the **Site Communication** overview, confirm:

- Ethernet / network settings are correct
- RS485 roles are correct (Follower is set, if applicable)
- Modbus TCP is visible and set to **1502**
- **Power Reduction Interface (RRCR):** Enabled