# Sungrow Logger1000

This guide is for installers configuring a **Sungrow Logger 1000 (EU)** so Octave's EMS can perform **solar curtailment** (and other active power services) via **Modbus TCP**.

## Supported assets

| Model | Modbus TCP | Modbus RTU | Validated |
| --- | :---: | :---: | :---: |
| Logger1000 |  |  |  |

## Prerequisites

- SmartLogger 1000 is powered on and connected to the network.
- Your laptop/PC is on the **same network** as the SmartLogger.
- Web browser (Chrome / Edge / Firefox).
- Installer / O&amp;M credentials.
- Network access to **Modbus TCP port 502**.

## Configure SmartLogger for remote active power control

1. Open a browser and go to the SmartLogger WebUI:

   ```text
   http://<SmartLogger-IP>
   ```
2. Log in with an **installer / administrator** account.
3. In the left menu, navigate to **Power control → Active power**.
4. Under **Active power control mode**, set:

   ```text
   Remote power control
   ```

[![Image](<https://docs.octave.energy/ems/integrations/assets/sungrow-logger1000/20fe3491-image.png>)](<https://docs.octave.energy/ems/integrations/assets/sungrow-logger1000/20fe3491-image.png>)

1. Configure the following parameters and **Save**:

   | Parameter | Value |
   | --- | --- |
   | Control strategy | Open-loop control |
   | Query recovery time | 1 s |
   | Frame delay | 18 ms |

[![Image](<https://docs.octave.energy/ems/integrations/assets/sungrow-logger1000/ae1f9d32-image.png>)](<https://docs.octave.energy/ems/integrations/assets/sungrow-logger1000/ae1f9d32-image.png>)

## Verify Modbus TCP connectivity (port 502)

- Sungrow SmartLogger uses **Modbus TCP on port 502** by default.
- Ensure:

  - Port **502** is open on the network path between Octave / site network and the SmartLogger.
  - No firewall blocks inbound Modbus TCP requests.

## Find the Device Communication ID (required)

1. In the left menu, open **Device maintenance → Device list**.
2. In the **Device List** table, locate the following columns:

   - Device name / model
   - Port (COMx)
   - Device address
   - Communication address
   - Modbus forwarding address
   - Communication status
3. The **Device Communication ID** is the value shown as **Communication Address / Modbus Forwarding Address**.
4. Take a screenshot of the table with these fields visible, including the green communication status indicator.

[![Image](<https://docs.octave.energy/ems/integrations/assets/sungrow-logger1000/a16b5257-image.png>)](<https://docs.octave.energy/ems/integrations/assets/sungrow-logger1000/a16b5257-image.png>)

## Verify inverter accepts remote power regulation

1. Go to **Device monitoring**.
2. Select an inverter.
3. Open **Power regulation parameters**.
4. Confirm:

   - Power control parameters are enabled.
   - No local override blocks remote commands.

[![Image](<https://docs.octave.energy/ems/integrations/assets/sungrow-logger1000/b26e4d19-image.png>)](<https://docs.octave.energy/ems/integrations/assets/sungrow-logger1000/b26e4d19-image.png>)

[![Image](<https://docs.octave.energy/ems/integrations/assets/sungrow-logger1000/6f0ab755-image.png>)](<https://docs.octave.energy/ems/integrations/assets/sungrow-logger1000/6f0ab755-image.png>)

## Deliverable for onboarding passport

Provide the screenshot from **Device maintenance → Device list** clearly showing:

- Device Name
- Device Model
- COM Port
- Communication Address / Modbus Address
- Green communication status indicator

## Notes

- This configuration enables Octave's EMS to send active power commands to the site via the SmartLogger.
- If multiple inverters are connected, each inverter typically has a unique COM port and Modbus communication address.