| 40070 | | Octave Battery Model | | group | | | | | | | |
| 0 | | 40070 | ID | 65301 | uint16 | 1 | | | R | Y | Model ID | Model identifier |
| 1 | | 40071 | L | 68 | uint16 | 1 | | | R | Y | Model Length | Model length |
| 2 | | 40072 | VAMax | | uint16 | 1 | P_SF | VA | R | Y | Maximum apparent power | Maximum apparent power |
| 3 | | 40073 | WChaMax | | int16 | 1 | P_SF | W | R | Y | Max Charging Power | Maximum instantaneous active charging power considering battery, inverter and site limits. A negative value means the battery should discharge with at minimum this value to respect e.g. the site limits. |
| 4 | | 40074 | WDisChaMax | | int16 | 1 | P_SF | W | R | Y | Max Discharging Power | Maximum instantaneous active discharging power considering battery, inverter and site limits. A negative value means the battery should charge with at minimum this value to respect e.g. the site limits. |
| 5 | | 40075 | WMeas | | int16 | 1 | P_SF | W | R | Y | AC active power | AC active power measured by the inverter |
| 6 | | 40076 | VAMeas | | int16 | 1 | P_SF | VA | R | Y | AC apparent power | AC apparent power measured by the inverter |
| 7 | | 40077 | VARMeas | | int16 | 1 | P_SF | VAR | R | Y | AC reactive power | AC reactive power measured by the inverter |
| 8 | | 40078 | PFMeas | | int16 | 1 | PF_SF | Pct | R | Y | AC power factor | AC power factor measured by the inverter. IEEE convention: positive is leading (capacitive), negative is lagging (inductive). |
| 9 | | 40079 | SoC | | int16 | 1 | SoC_SF | %WHRtg | R | Y | Battery State of Charge | Battery State of Charge |
| 10 | | 40080 | InverterState | | enum16 | 1 | | | R | Y | Inverter state | Inverter state |
| | | Off | 1 | | | | | | | | Off |
| | | Precharge | 2 | | | | | | | | Precharge |
| | | Standby | 3 | | | | | | | | Standby |
| | | Starting | 4 | | | | | | | | Starting |
| | | Grid_connected | 5 | | | | | | | | Grid_connected |
| | | Throttled | 6 | | | | | | | | Throttled |
| | | Error | 7 | | | | | | | | Error |
| | | Unknown | 99 | | | | | | | | Unknown |
| 11 | | 40081 | BMSState | | enum16 | 1 | | | | Y | BMS State | BMS State |
| | | ok | 1 | | | | | | | | OK |
| | | startup | 2 | | | | | | | | Starting up |
| | | alert | 3 | | | | | | | | Alert, but Octave Cabinet can still be operated (e.g. low temperature) |
| | | alert no charge | 4 | | | | | | | | Voltages too high, only discharge |
| | | alert no discharge | 5 | | | | | | | | Voltages too low, only charge |
| | | alert stop | 6 | | | | | | | | Alert, stopping inverter. Temperature too high or other fault |
| | | emergency | 7 | | | | | | | | Emergency, switching contactors immediately |
| | | error | 8 | | | | | | | | BMS error, inverter should stop |
| | | shutdown | 9 | | | | | | | | Shut down |
| | | unknown | 0 | | | | | | | | Unknown |
| 12 | | 40082 | NStr | | uint16 | 1 | | | R | Y | String Count | |
| 13 | | 40083 | NStrConn | | uint16 | 1 | | | R | Y | Connected String Count | |
| 14 | | 40084 | WHRtg | | uint16 | 1 | WHRtg_SF | Wh | R | Y | Nominal Energy Capacity | |
| 15 | | 40085 | SoH | | int16 | 1 | SoC_SF | %WHRtg | R | Y | State of Health | |
| 16 | | 40086 | AvailWHRtg | | uint16 | 1 | WHRtg_SF | Wh | R | Y | Available Nominal Energy Capacity | |
| 17 | | 40087 | WMax | | uint16 | 1 | WMax_SF | W | R | | Nominal Power | |
| 18 | | 40088 | AvailWMax | | uint16 | 1 | WMax_SF | W | R | | Available Nominal Power | |
| 19 | | 40089 | CellTmpMin | | int16 | 1 | Tmp_SF | °C | R | | Min cell temperature, across the whole battery plant | |
| 20 | | 40090 | CellTmpMax | | int16 | 1 | Tmp_SF | °C | R | | Max cell temperature, across the whole battery plant | |
| 21 | | 40091 | AvailWH | | uint16 | 1 | WHRtg_SF | Wh | R | | Remaining (dischargeable) Energy Capacity | |
| 22 | | 40092 | Watchdog | | uint16 | 1 | | | RW | Y | Watchdog petting | In external control, watchdog needs to be written every 10 seconds or system will turn to a zero power setpoint |
| 23 | | 40093 | PowerCtrl | | enum16 | 1 | | | RW | Y | Power control mode | Power control mode |
| | | Default control | 1 | | | | | | | | Default battery power control. |
| | | External power setpoint control | 90 | | | | | | | | System will listen to external power setpoints Wset and VARSet. |
| | | External reactive setpoint control | 91 | | | | | | | | System will listen to external reactive power setpoints VARSet, but use its internal controller for the active power setpoint. The reactive power setpoint will have priority and if needed limit the active power. |
| 24 | | 40094 | WSet | | int16 | 1 | P_SF | W | RW | Y | Active power setpoint | Active power setpoint. Positive is charging, negative is discharging. |
| 25 | | 40095 | VARSet | | int16 | 1 | P_SF | VAR | RW | Y | Reactive power setpoint | Reactive power setpoint. Positive is capacitive. Negative is inductive. |
| 26 | | 40096 | WChaLim | | uint16 | 1 | P_SF | W | RW | Y | Active power charging limit | Set Active power charging limits. Applicable in all control modes |
| 27 | | 40097 | WDisChaLim | | uint16 | 1 | P_SF | W | RW | Y | Active power discharging limit | Set Active power discharging limits. Applicable in all control modes |
| 28 | | 40098 | VALim | | uint16 | 1 | P_SF | VA | RW | Y | Apparent power limit | Set apparent power limits. Applicable in all control modes |
| 29 | | 40099 | Placeholder | | | 12 | | | | Y | Reserved | |
| 41 | | 40111 | WInjLimAct | | enum16 | 1 | | | RW | Y | Active power injection limit active | Write 1 to activate active power injection power limit into the grid |
| | | Injection limit control off | 0 | | | | | | | | Injection limit control off |
| | | Injection limit control on | 1 | | | | | | | | Injection limit control on |
| 42 | | 40112 | WInjLim | | uint16 | 1 | PG_SF | W | RW | Y | Active power injection limit | Grid injection power limit as described in Synergrid 7.22.2.2 |
| 43 | | 40113 | WOffLimAct | | enum16 | 1 | | | RW | Y | Active power offtake limit active | Write 1 to activate active power offtake limit from the grid |
| | | Offtake limit control off | 0 | | | | | | | | Offtake limit control off |
| | | Offtake limit control on | 1 | | | | | | | | Offtake limit control on |
| 44 | | 40114 | WOffLim | | uint16 | 1 | PG_SF | W | RW | Y | Active power offtake limit | Grid offtake power limit |
| 45 | | 40115 | QGridSetAct | | enum16 | 1 | | | RW | Y | Grid reactive power setpoint active | Write 1 to activate grid reactive power setpoint |
| | | Grid reactive power setpoint control off | 0 | | | | | | | | Grid reactive power setpoint control off |
| | | Grid reactive power setpoint control on | 1 | | | | | | | | Grid reactive power setpoint control on |
| 46 | | 40116 | QGridSet | | int16 | 1 | PG_SF | VAR | RW | Y | Grid reactive power setpoint | Grid reactive power setpoint |
| 47 | | 40117 | Placeholder | | | 8 | | | | Y | Reserved | |
| 55 | | 40125 | P_SF | 2 | sunssf | 1 | | | R | Y | | Power scaling factor |
| 56 | | 40126 | PG_SF | 2 | sunssf | 1 | | | R | Y | | Grid Power Limit scaling factor |
| 57 | | 40127 | SoC_SF | -1 | sunssf | 1 | | | R | Y | | SoC Scaling Factor |
| 58 | | 40128 | PF_SF | -1 | sunssf | 1 | | | R | Y | | Power Factor scaling factor |
| 59 | | 40129 | WHRtg_SF | 3 | sunssf | 1 | | | R | Y | | (Nominal) Energy Capacity scaling factor |
| 60 | | 40130 | WMax_SF | 3 | sunssf | 1 | | | R | Y | | Nominal power scaling factor |
| 61 | | 40131 | Tmp_SF | 0 | sunssf | 1 | | | R | Y | | Temperature scaling factor |
| 62 | | 40132 | Placeholder | | | 7 | | | | Y | Reserved | |
| 69 | | 40139 | Pad | | pad | 1 | | | | Y | | Pad register. |