65301 - Octave Battery Model#

Address Offset Group Offset Register Address Name Value Type Size Scale Factor Units RW Access (RW) Implemented? Label Description
40070 Octave Battery Model group
0 40070 ID 65301 uint16 1 R Y Model ID Model identifier
1 40071 L 68 uint16 1 R Y Model Length Model length
2 40072 VAMax uint16 1 P_SF VA R Y Maximum apparent power Maximum apparent power
3 40073 WChaMax int16 1 P_SF W R Y Max Charging Power Maximum instantaneous active charging power considering battery, inverter and site limits. A negative value means the battery should discharge with at minimum this value to respect e.g. the site limits.
4 40074 WDisChaMax int16 1 P_SF W R Y Max Discharging Power Maximum instantaneous active discharging power considering battery, inverter and site limits. A negative value means the battery should charge with at minimum this value to respect e.g. the site limits.
5 40075 WMeas int16 1 P_SF W R Y AC active power AC active power measured by the inverter
6 40076 VAMeas int16 1 P_SF VA R Y AC apparent power AC apparent power measured by the inverter
7 40077 VARMeas int16 1 P_SF VAR R Y AC reactive power AC reactive power measured by the inverter
8 40078 PFMeas int16 1 PF_SF Pct R Y AC power factor AC power factor measured by the inverter. IEEE convention: positive is leading (capacitive), negative is lagging (inductive).
9 40079 SoC int16 1 SoC_SF %WHRtg R Y Battery State of Charge Battery State of Charge
10 40080 InverterState enum16 1 R Y Inverter state Inverter state
Off 1 Off
Precharge 2 Precharge
Standby 3 Standby
Starting 4 Starting
Grid_connected 5 Grid_connected
Throttled 6 Throttled
Error 7 Error
Unknown 99 Unknown
11 40081 BMSState enum16 1 Y BMS State BMS State
ok 1 OK
startup 2 Starting up
alert 3 Alert, but Octave Cabinet can still be operated (e.g. low temperature)
alert no charge 4 Voltages too high, only discharge
alert no discharge 5 Voltages too low, only charge
alert stop 6 Alert, stopping inverter. Temperature too high or other fault
emergency 7 Emergency, switching contactors immediately
error 8 BMS error, inverter should stop
shutdown 9 Shut down
unknown 0 Unknown
12 40082 NStr uint16 1 R Y String Count
13 40083 NStrConn uint16 1 R Y Connected String Count
14 40084 WHRtg uint16 1 WHRtg_SF Wh R Y Nominal Energy Capacity
15 40085 SoH int16 1 SoC_SF %WHRtg R Y State of Health
16 40086 AvailWHRtg uint16 1 WHRtg_SF Wh R Y Available Nominal Energy Capacity
17 40087 WMax uint16 1 WMax_SF W R Nominal Power
18 40088 AvailWMax uint16 1 WMax_SF W R Available Nominal Power
19 40089 CellTmpMin int16 1 Tmp_SF °C R Min cell temperature, across the whole battery plant
20 40090 CellTmpMax int16 1 Tmp_SF °C R Max cell temperature, across the whole battery plant
21 40091 AvailWH uint16 1 WHRtg_SF Wh R Remaining (dischargeable) Energy Capacity
22 40092 Watchdog uint16 1 RW Y Watchdog petting In external control, watchdog needs to be written every 10 seconds or system will turn to a zero power setpoint
23 40093 PowerCtrl enum16 1 RW Y Power control mode Power control mode
Default control 1 Default battery power control.
External power setpoint control 90 System will listen to external power setpoints Wset and VARSet.
External reactive setpoint control 91 System will listen to external reactive power setpoints VARSet, but use its internal controller for the active power setpoint. The reactive power setpoint will have priority and if needed limit the active power.
24 40094 WSet int16 1 P_SF W RW Y Active power setpoint Active power setpoint. Positive is charging, negative is discharging.
25 40095 VARSet int16 1 P_SF VAR RW Y Reactive power setpoint Reactive power setpoint. Positive is capacitive. Negative is inductive.
26 40096 WChaLim uint16 1 P_SF W RW Y Active power charging limit Set Active power charging limits. Applicable in all control modes
27 40097 WDisChaLim uint16 1 P_SF W RW Y Active power discharging limit Set Active power discharging limits. Applicable in all control modes
28 40098 VALim uint16 1 P_SF VA RW Y Apparent power limit Set apparent power limits. Applicable in all control modes
29 40099 Placeholder 12 Y Reserved
41 40111 WInjLimAct enum16 1 RW Y Active power injection limit active Write 1 to activate active power injection power limit into the grid
Injection limit control off 0 Injection limit control off
Injection limit control on 1 Injection limit control on
42 40112 WInjLim uint16 1 PG_SF W RW Y Active power injection limit Grid injection power limit as described in Synergrid 7.22.2.2
43 40113 WOffLimAct enum16 1 RW Y Active power offtake limit active Write 1 to activate active power offtake limit from the grid
Offtake limit control off 0 Offtake limit control off
Offtake limit control on 1 Offtake limit control on
44 40114 WOffLim uint16 1 PG_SF W RW Y Active power offtake limit Grid offtake power limit
45 40115 QGridSetAct enum16 1 RW Y Grid reactive power setpoint active Write 1 to activate grid reactive power setpoint
Grid reactive power setpoint control off 0 Grid reactive power setpoint control off
Grid reactive power setpoint control on 1 Grid reactive power setpoint control on
46 40116 QGridSet int16 1 PG_SF VAR RW Y Grid reactive power setpoint Grid reactive power setpoint
47 40117 Placeholder 8 Y Reserved
55 40125 P_SF 2 sunssf 1 R Y Power scaling factor
56 40126 PG_SF 2 sunssf 1 R Y Grid Power Limit scaling factor
57 40127 SoC_SF -1 sunssf 1 R Y SoC Scaling Factor
58 40128 PF_SF -1 sunssf 1 R Y Power Factor scaling factor
59 40129 WHRtg_SF 3 sunssf 1 R Y (Nominal) Energy Capacity scaling factor
60 40130 WMax_SF 3 sunssf 1 R Y Nominal power scaling factor
61 40131 Tmp_SF 0 sunssf 1 R Y Temperature scaling factor
62 40132 Placeholder 7 Y Reserved
69 40139 Pad pad 1 Y Pad register.