65302 - Octave PV Model#

Address Offset Group Offset Register Address Name Value Type Size Scale Factor Units RW Access (RW) Label Description
40140 Octave PV Model group
0 40140 ID 65302 uint16 1 R Model ID
1 40141 L 68 uint16 1 R Model Length
2 40142 VAMax uint16 1 P_SF VA R Rated apparent power
3 40143 WMeas int16 1 P_SF W R AC active power
4 40144 VAMeas uint16 1 P_SF VA R AC apparent power
5 40145 VARMeas int16 1 P_SF VAR R AC reactive power
6 40146 PFMeas int16 1 PF_SF Pct R AC power factor
7 40147 State enum16 1 R Inverter/Logger state
OFF 1
FAULT 2
RUNNING 3
UNKNOWN 4
8 40148 Placeholder 14 Reserved
22 40162 Watchdog uint16 1 RW Watchdog petting In external control, watchdog needs to be written every 10 seconds or control will fallback to default behaviour
23 40163 Placeholder 3 Reserved
26 40166 WLim uint16 1 P_SF W RW Active power limit Set active power production limit of PV Plant
27 40167 VARSet int16 1 P_SF VAR RW Reactive power limit Set reactive power production limit of PV Plant
28 40168 Placeholder 13 Reserved
41 40181 WInjLimAct enum16 1 RW Active power injection limit active Write 1 to activate active power injection power limit into the grid
Injection limit control off 0 Injection limit control off
Injection limit control on 1 Injection limit control on
42 40182 WInjLim uint16 1 PG_SF W RW Active power injection limit Grid injection power limit as described in Synergrid 7.22.2.2
43 40183 Placeholder 12 Reserved
55 40195 P_SF 2 sunssf 1 R Power scaling factor
56 40196 PG_SF 3 sunssf 1 R Grid power scaling factor
57 40197 PF_SF -1 sunssf 1 R Power factor scaling factor
58 40198 Placeholder 11 Reserved
69 40209 Pad pad 1 Pad register